fbpx

SL-2000-P SUPPORT PAGE

Duct Detector Troubleshooting | SL-2000 duct detector wiring |Detectors tech support

Learn how to troubleshoot a smoke duct detector. Smoke detector wiring and interconnecting. Remote controls compatibility.

A Halma Company.

Interconnect Wiring
Fire Alarm Wiring
Residential Furnace Wiring
Remote Annunciator Wiring
Remote Horn/Strobe Alarm Wiring
Electrical Contractor Wiring
HVAC Contractor Wiring

INTERCONNECT WIRING

Watch this video to see how to connect two SL-2000 duct smoke detectors together:


preview of sl2000 wiring

 

 

⇒ FIRE ALARM WIRING

Watch this video to see how to connect a SL-2000 duct smoke detector to a fire alarm control panel:

 

FireAlarmConnectDiagram 

⇒ RESIDENTIAL FURNACE WIRING

Some newer furnaces will continue to run the fan after call for heat signal is broken sometimes called a fan run-down, this can sometimes be programmed via DIP switches on the furnace board. Use below configurations where it is unable to be turned off.

 

⇒ REMOTE ANNUNCIATOR WIRING

Reminder LED indicators on MS series remotes are polarity sensitive, always ensure the black wire is connected to terminal 19.

Please note LED indicators on MS series remotes are polarity sensitive, always ensure the black wire is connected to terminal 19.

 

⇒ ELECTRICAL CONTRACTOR WIRING

⇒ HVAC CONTRACTOR WIRING

SL-2000

testing

Testing options:

  1. Magnehelic differential pressure gauge between the sampling and exhaust tubes of the detector, a reading between 0.01 and 1.2 inches of water verifies enough airflow;
  2. Spraying TG-2000 test gas into the test port of the detector, an alarm would be expected;
  3. Using the included test magnet on the top of the duct smoke detector housing between the 2 marked lines indicated on lid, again an alarm would be expected to confirm correct operation;
  4. Testing from a remote;
  5. The detector control board and relays can be tested for correct operation by pressing the black test/reset button in the transparent lid hole, an alarm condition would verify correct operation (red LED on board).
SL-2000

remotes

Remotes Guide

Duct detector remotes

Learn about APC remotes compatibility..

SL-2000

troubleshooting

No lights:smoke detector is powered but no lights

Troubleshoot with these steps:

  1. Check power is good, probe across terminals 9 and 10, check for roughly 24V;
  2. Check detector head is seated, rotate counterclockwise and reattach it by turning clockwise until its seated;
  3. Check transparent lid, ensure it is fitted and not ajar and all screws are tightened, SW1 can be inspected for damage if the lid has been installed incorrectly previously.

 

 

Troubleshooting:Pilot LED will not turn on

Check power is good, probe across terminals 9 and 10, check for roughly 24V.

Check detector head is seated, rotate counterclockwise and reattach it by turning clockwise until its seated.

Check transparent lid, ensure it is fitted and not ajar and all screws are tightened, SW1 can be inspected for damage if the lid has been installed incorrectly previously.

Mount direction:Can the duct detector be mounted any direction?

Duct smoke detectors can be mounted any way either vertically or horizontally if the sampling tube holes are facing the direction of airflow.

Sampling tube sizing:what size must my sampling tubes be?

NFPA72 recommends all sampling tubes to be at least 80% of the duct width i.e. if your duct is 12 inches wide, the sampling tube must be at least 9.6 inches long.

Any tube over 3ft must be supported.

Tubes can be cut down for the correct size, but metal tubes have different hole spacing based on its size.

The 10inch tube has holes spaced closer together than a 5 ft tube. Therefore, you cannot cut a longer tube shorter than its recommended duct size or there will not be a correct amount of air sampled from the duct work.

 

Sensitivity TestHow can I sensitivity test detector heads?

Recommended procedure is removing detector head and running on external 24V power supply and detector base using an SDI Trutest 801 for testing sensitivity.

Alarm malfunction:Detector goes straight into alarm

In case of old installation:

check the detector head and housing for excessive dust. Detectors can be blown out with compressed air or replacement detector heads ordered, 55000-328 for -P model or 55000-225 for the -N model.

If detector is interconnected to another detector in the system:

This can be checked by looking to see if there are wires on terminals 12 and 20, check to see if the other detector is maybe in alarm.

If its a new installation:

If detector has been wired to a remote or accessories remove wiring such that only power is connected, if it stops going into alarm confirm correct wiring for model of remote when reattaching and that key switch is not activated.

In situations of high humidity or temperature swings such as in sunbelt states condensation can build up on and inside detectors which can cause false alarms, we recommend moving a detector further downstream on ductwork or inside building where temperature swings might not be as extreme.

 If detector still goes into alarm when all wiring removed, replace detector head or RMA unit. 

For RMA request click here: RMA request.

Shut down furnace or RTU:How can I use the detector to shut down a residential furnace or commercial rooftop unit?

Alarm contact terminals 16 and 6 (normally closed and common) can be used to break the red 24V power wire to the thermostat.

16 and 6 effectively works as a switch, in a normal condition 16 is connected to 6 and when in alarm 16 is disconnected from 6.

Some residential furnaces have a fan rundown mode where the fan will run even after a signal from the thermostat, these furnaces sometimes have a DIL switch to program this feature or alternatively power can be broken to the furnace alternate to the thermostat by breaking the neutral power to the furnace through terminals 16 and 6.

See Wiring diagrams here: Wiring Diagrams

Detector is chattering when it goes into alarm

Breaking same power used to power detector when in alarm. Use a separate 24VAC transformer, power supply or mains power.

Remote not working

MSR50/100 based remotes wire to SL2000.

If wiring is correct, check for shorted or open circuit wires pulled from detector to the remote. Multimeter can be used to continuity test wires if disconnected from detector and remote and twisted together in pairs.

SL2000 MSR50/100
20 C+
1 T/R
2 P+
12 AL+
19 C-
4 TB+

Remote compatibilityCan I use a System Sensor remote?

Air product and controls duct smoke detectors are not compatible, or UL listed to work with System Sensor or other manufacturer’s remotes.

Please see here our remotes compatibility info: Remotes

How tointerconnect duct smoke detectors (common alarm)?

SL2000 terminals 12 and 20 must be connected between all detectors desired to be interconnected, a common power source must be used such that all detectors interconnected must be powered from a common 24VAC transformer, or mains power circuit.

For a common remote for common test/reset, 12 and 20 must be connected between all desired detectors.

How to:connect a duct smoke detector to a fire alarm control panel?

In a typical class B fire alarm configuration wire one wire from your fire alarm panel to terminal 13 and the other to 14. Make a wire jumper from terminal 13 to terminal 5 and place your end of line resistor to terminals 14 and 15.

For applications of multiple duct smoke detectors on a single fire alarm circuit, all alarm contacts must be wired to the panel in parallel with all trouble contacts wired in series with the end of line resistor on the very last detector. Refer to Page 4 of the installation guide for wiring diagram.

How to:connect a fire alarm panel interface to remotely reset the detector?

Normally open and common relay contacts on the fire alarm interface can be connected to terminals 1 and 20 on the SL2000 duct smoke detector.

How to:test and confirm correct installation and operation of my duct smoke detector?

Correct airflow can be confirmed with the use of a magnehelic differential pressure gauge between the sampling and exhaust tubes of the detector, a reading between 0.01 and 1.2 inches of water verifies enough airflow.

The detector head can be tested for correct operation by spraying TG-2000 test gas into the test port of the detector, an alarm would be expected. Continued testing also includes using the included test magnet on the top of the duct smoke detector housing between the 2 marked lines indicated on lid, again an alarm would be expected to confirm correct operation.

The detector control board and relays can be tested for correct operation by pressing the black test/reset button in the transparent lid hole, an alarm condition would verify correct operation (red LED on board).

See video here: VIDEO