Wiring the SL-2000 as a fire system contractor

  • In a typical class B fire alarm configuration wire one wire from your fire alarm panel to terminal 13 and the other to 14. Make a wire jumper from terminal 13 to terminal 5 and place your end of line resistor to terminals 14 and 15.
  • For applications of multiple duct smoke detectors on a single fire alarm circuit, all alarm contacts must be wired to the panel in parallel with all trouble contacts wired in series with the end of line resistor on the very last detector. Refer to Page 4 of the installation guide for wiring diagram.