A starter tube included in your detector box which friction fits with the grey and red connectors on the tubes included with FAST Tubes
Tubes can be cut with a small hack saw or with box cutter
Sampling tubes should cover at least 80% of the width of the duct work
Sampling tubes should cover at least 80% of the width of the duct work
All duct detectors should be installed with a sampling tube covering at least 80% the width of the duct work and a sampling tube for correct operation
FAST Tubes are made of a flame retardant polycarbonate with a melting point well beyond the maximum that can be found in a HVAC system
All duct detectors should be installed with both sampling and exhaust tubes to operate correctly
Spare sections of FAST tubes can be kept for combining with other sections in jobs with wide duct work
The red end cap should be installed at the cut end of the sampling tube when assembly is complete
FAST tubes can be used on all models of our duct detectors
You will have to order FAST tubes or STM tubes separate, though the starter stub and exhaust tube is included in the box of the detector
FAST Tubes use a Flame retardant and UV stabilized polycarbonate which will not degrade in its life
FAST Tubes are recommended in all new applications due to light weight and ease of use
FAST Tubes are manufactured in the USA
FAST Tubes are listed to work on all our UL268A duct detectors
STM sampling tubes are compatible with all models of our duct detectors
STM tubes are constructed of galvanized steel and are designed to resist rusting though might corrode in harsh environments
STM Tubes are manufactured in the USA
STM tubes are listed to work on all our UL268A duct detectors