PAM-1 – 24VAC, 24VDC, 120VAC
PAM-2 – 12VDC, 24VDC
PAM-4 -12-40VDC for EOL circuits
PAM-SD – 20-32VDC ideal for NAC circuits
PAM relays are designed for fire alarm signal and control applications
PAM relays act as an electronic switch and allow electrical signals to control an isolated dry relay contact
PAM-1 – 50mA @ 24VAC, 20mA @ 24VDC, 50mA @ 120VAC
PAM-2 – 20mA @ 12VDC, 20Ma @ 24VDC
PAM-4 -20Ma @ 12-40VDC
PAM-SD – 15-25Ma @ 20-32VDC
The RED status LED indicates when the relay is energized
All PAM series relays are listed to UL864
The PAM relays are imported
Common is connected to normally closed when not energized, and common is connected to normally open when energized
The PAM series relays no not output voltage and offer only a dry relay contact
Relays have an internal armature which changes from connecting common to normally closed, to connecting common to normally open when energized
APC cannot comment on how the relay is wired, only thing we can help you with is the functioning of the relay.
Control wires control the switching of the relay and the output wires are connected to the dry internal relay contact which is the circuit that is being controlled. The control circuit and the output circuit are fully isolated.
All spare wires should be wirenut terminated
Relays are ideal for applications where a low voltage signal needs to control a high voltage signal and vice versa or a full isolation is required between the control circuit and the external connections.
The MR-100 Series relays are multi-voltage relays offered in a grey enclosure, a red enclosure or on plastic track. The PAM relays are small encapsulated relays with flying leads.
MR relays act as an electronic switch and allow electrical signals to control an isolated dry relay contact
24VDC. this is powered from the wiring connections from the duct detector
The RED status LED indicates when the relay is energized
MR relays are manufactured in the USA
All MR series relays are listed to UL864
to wire to a SL-2000 use the following wiring connections: C+ to 20, T/R to 1, P+ to 2, AL+ to 11, C- to 19.
Common is connected to normally closed when not energized, and common is connected to normally open when energized
The MR series relays no not output voltage and offer only a dry relay contact