In all cases the Codes state that installations, tests and inspections shall be made in accordance with the manufacturer’s published instructions. The illustration above shows two sample air duct smoke detector installations. Both are “clean” installations, however only the detector to the left has been set up to properly monitor the airstream sample as required by the IMC (Chapter 606.3) and NFPA 72® (Chapter 5.16.5.2). NFPA90A Chapter 6 requires that smoke detectors be installed, tested and maintained in accordance with NFPA 72, National Fire Alarm Code®.
Designed to Save Lives
Many people fail to remember that more people are killed by smoke inhalation than by fire. If the installations you are responsible for fail because the deadly smoke stream by-passed the sample tube and did not trigger sensor head alarm and system shutdown (or other functions), you may face liability. In addition to monetary losses, think about the lives that may be lost or in jeopardy. It’s simply not worth it to install short tubes and “sneak it past” the Building Inspector to save your time and cost, nor is it legal to do so.